DIMENSION
.png)

SPECIFICATION
Nominal Voltage:12V 
Dimension
Length: 508±3mm
Width: 106±3mm
Case Height: 236±3mm
Overall Height: 236±3mm 
Weight(Approx.):34 kg
Nominal Capacity:100AH / 10HR(25°C) 
​
Internal Resistance(Approx.): 3.5 mΩ 
​
Max. Charge current:25A  5
Max. Discharge current in 5 seconds:600A 
Float Charging:13.65±0.15V(25°C) 
Terminal
Top terminal: Bolt(M6)
Front terminal:Bolt(M6)
Operating Temperature Range
Discharging -15°C to 45°C
Charging -15°C to 45°C
Storage -15°C to 45°C 
Expected float use life(25°C):10 years 
Easy Maintenance
No electrolyte leakage
Ensure safe and efficient operation 
Vent plug provided with built-in ceramic filter
Prevent explosion from outside source of ignition 
Container Material
ABS Flame Retardant ABS,Flame class:UL94V0 Oxygen index:28.0% LOI 
Handle Including 
Applications
UPS
UPS(Uninterruptible Power Supply), Telecommunications, Emergency lighting, Alarm systems, Instrumentation,Solar powered systems